A是协调器
B、C、D、E、F 是终端
使用Z-Tool通过串口连接协调器A发送MT_ZDO_BIND_REQ命令
希望终端B、C、D、E、F控制协调器A
实际只能头4个终端可以bind。
Susan Yang:
绑定表的大小可以通过f8wConfig.cfg中的【NWK_MAX_BINDING_ENTRIES和MAX_BINDING_CLUSTER_IDS】来进行配置
请问您这些参数是怎样配置的?
zixin fan:
回复 Susan Yang:
谢谢回复!
1、 单独 -DNWK_MAX_BINDING_ENTRIES=8
还是bind不上
2、单独 -DMAX_BINDING_CLUSTER_IDS=8
编译出错
Linking Warning[w6]: Type conflict for external/entry "GetBindingTableEntry", in module APS against external/entry in module BindingTable; function return types are different; class/struct/union types have different sizes Warning[w6]: Type conflict for external/entry "bindFind", in module APS against external/entry in module BindingTable; function return types are different; class/struct/union types have different sizes Warning[w6]: Type conflict for external/entry "bindFindExisting", in module APS against external/entry in module BindingTable; function return types are different; class/struct/union types have different sizes Warning[w6]: Type conflict for external/entry "bindIsClusterIDinList", in module APS against external/entry in module BindingTable; function types differ in parameter 1; class/struct/union types have different sizes Warning[w6]: Type conflict for external/entry "bindRemoveClusterIdFromList", in module APS against external/entry in module BindingTable; function types differ in parameter 1; class/struct/union types have different sizes Warning[w6]: Type conflict for external/entry "bindRemoveEntry", in module APS against external/entry in module BindingTable; function types differ in parameter 1; class/struct/union types have different sizes Warning[w6]: Type conflict for external/entry "pbindAddEntry", in module APS against external/entry in module BindingTable; function return types are different; class/struct/union types have different sizes
zixin fan:
回复 zixin fan:
仔细在第5个终端分析发现:
协调器执行ZDO_BIND_REQ之后
第5终端会执行
clusterID:0x0021
case Bind_req: case Unbind_req: { ZDO_BindUnbindReq_t bindReq; ZDO_ParseBindUnbindReq( inMsg, &bindReq ); ZDO_ProcessBindUnbindReq( inMsg, &bindReq ); }
之后就没有了。
———————————-
而之前4个终端正常bind的时候会执行
clusterID:0x0021
case Bind_req:case Unbind_req:{ZDO_BindUnbindReq_t bindReq;ZDO_ParseBindUnbindReq( inMsg, &bindReq );ZDO_ProcessBindUnbindReq( inMsg, &bindReq );}
之后还会执行
clusterID:0x8000
case NWK_addr_rsp:case IEEE_addr_rsp: {。。。。
if ( inMsg->clusterID == NWK_addr_rsp ) {#if defined ( REFLECTOR ) ZDApp_ProcessPendingBindReq( pAddrRsp->extAddr );#endif }#endif
osal_mem_free( pAddrRsp ); } }
zixin fan:
回复 zixin fan:
继续分析第5个终端不能正常bind的代码
执行到ZDO_ProcessBindUnbindReq( inMsg, &bindReq ); –>ZDP_NwkAddrReq( pReq->dstAddress.addr.extAddr, ZDP_ADDR_REQTYPE_SINGLE, 0, 0 );
应该是向协调器发送NWKADDr请求,协调器没有反馈。
为什么第5个终端没有像之前4个终端请求NWKADDr有反馈呢
zixin fan:
回复 Susan Yang:
附件中
终端作为第5个要bind失败的终端抓包
zixin fan:
回复 zixin fan:
已经解决了,自己的程序写错了。谢谢 Susan Yang !
Susan Yang:
回复 zixin fan:
很高兴您能解决问题!
user5301288:
回复 zixin fan:
请问你这个最后怎么解决的,我也遇到了和你一样的问题,有3个端点,其中一个绑定不成功,状态时table full.
YiKai Chen:
回复 user5301288:
把NWK_MAX_BINDING_ENTRIES加大試試
user5301288:
回复 YiKai Chen:
您好!
我把原先 NWK_MAX_BINDING_ENTRIES=4 改成 NWK_MAX_BINDING_ENTRIES=12,我开关的3个endpoint都绑定成功了。但是有时候会碰到状态同步不了,或是很慢。以前绑定2个还没有这样的情况。